Applications
Patented mechanical system of fire detection by liquid filled glass bulb breaking. In case of fire, when the temperature reaches the liquid boiling temperature, it causes the explosion of the glass bulb, which releases the mechanism.
This self-powered mechanism does not require power supply such as electricity or compressed air.
It can open smoke vents, skylights, in buildings, but also actuates fire doors, air conditioning dampers, store curtains, flammable gas or liquid valves, range hood exhausts, paint and solvent exhaust fans and dampers, etc.
Dimensions: Very small foot print, can replace most of devices using fusible links. In addition, having a very high tensile strength, this device does not require a demultiplying system.
Creep sensitivity: Insensitive to creep, even close to the tripping temperature.
ROHS compliance: For most of temperature calibration, fusible fire detection systems cannot be achieved, as they use alloys containing lead and cadmium, materials that are not allowed by the RoHS standard. This glass bulb operated device does not use fusible alloy and therefore contains no prohibited metal and meets the RoHS standard.
Material: Galvanized steel
Fail safe operation: When opening, the internal lever falls unhindered by any other part, irreversibly releasing the two halves of the mechanism.
This mechanism has no spring because, due to their susceptibility to corrosion and to permanent deformation, the use of springs may cause a malfunction.
Glass bulbs: Dia. 5mm, 16mm nominal length, filled with alcohol blends.
Response time index (RTI) of bare bulbs: <25 m.s1/2
Maximum permanent load: 100 DaN Tensile strength at break: ≥ 150 DaN
Minimum load: 5 DaN
Nominal opening temperatures: 57 °C (135 °F) orange bulb; 68 °C (155° F) red. The bulb coloring complies with EN 12259-1 and ISO 6182-1 international standards for color/temperature ratings. Other temperatures, please consult us.
Mounting: This model features
- one side with a hole allowing the connection either on a cable, or on a bracket integral with the opening (available as accessories)
- One side with integrated clamping device on steel cable, simplifying assembly.
Mounting position: When used in vertical position, the glass bulb must be downside. No preferential position when mounted horizontally.
Options: Rope thimble assembled on the 8mm hole
Glass bulb replacement: Replacement is possible, by using a locking pin, which must be removed after bulb replacement.
Certifications: according to ISO 10294-4.