Applications
- Equipment requesting the highest resistance to water ingress.
- The transparent cover allows to visualize the set point and the 2 pilot lights.
- Very small differential.
- Ultra compact enclosure
Temperature control with reduced differential, on-off action, in usual industrial applications and environments, not hazardous areas.
Use of electronic sensor allows measurement at long distances, which is not possible with bulb and capillary types.
Main features
Housing: Protection class IP69K upon EN60529 and DIN40050-9 (high pressure hot water, totally dust tight). Body in black PA66, fiber glass reinforced.
Hinged transparent polycarbonate window, with gasket. It can be unscrewed by hand, and has holes for safety seals.
IK10 shocks proof.
UV resistant.
Set point adjustment: By °C printed knob. All types have an adjustable rotation limit system located inside the knob that allows reducing the set point adjustment span. °F printed knobs available as an option.
Operation: Microprocessor electronic thermostat.
Sensing element: NTC or Pt100 sensor, 2m standard cable length. Others lengths on request.
Pilot lights: One pilot light visualizes the thermostat contact output position. The second visualizes the power supply input.
Set point adjustment ranges: -35-35°C (-30+95°F); 0-10°C (32-50°F); 4-40°C (40-105°F); 30-90°C (85-195°F); 30-110°C (85-230°F); 20-125°C (68-260°F); 50-200°C (120-390°F); 50-300°C (120-570°F); 100-400°C (210-750°F); 100-500°C (210-930°F).
Differential: Differential is preset at the minimum value, but can be increased with a potentiometer located under the set point adjustment knob.
Cable input and output: one M20 cable glands, black PA66.
Electrical connections: Inside, on screw terminal. Electronic control power supply in 220-250V.
Earthing: Internal screw terminal.
Mounting: Wall mounting, by 2 legs with holes for screws dia. 4mm, 60 × 65mm distance.
Identification: Identification label on backside
Contact: SPST. 16A (2.6), 250VAC. Open or close on temperature rise. Model with contact closing on temperature rise is used for refrigeration.
Version with contact opening on temperature rise is used for heating.
Electrical life: >100.000 cycles.
Minimum storage temperature: -35°C (-30°F)
Maximum ambient temperature: 60°C (140°F)
For more technical information see 2PE2N6 thermostat technical data sheet.